TRICONEX 3664 Dual digital output module
Specific Parameters
Electrical ParametersInput Voltage: 24V DC (±10% voltage tolerance)Output Type: 32 solid-state relay (SSR) outputsOutput Voltage: 24V DC (nominal), supporting 16-30V DC rangeOutput Current: 0.5A/channel (continuous), 10A/channel (transient)Response Time: 4ms (typical)Channel Isolation: Optocoupler isolation, 2500Vrms isolation voltageCommunication Protocols: Supports Modbus RTU/TCP, Tricon proprietary protocols
Mechanical ParametersOverall Dimensions: 175mm (L) × 114mm (W) × 32mm (H)Housing Material: Flame-retardant plastic (UL94 V-0 grade)Weight: 1.5kgMounting Method: 35mm DIN rail mounting, fits into Tricon system rack slotsStatus Indicators: 3 LED indicators (green: power normal; yellow: communication status; red: fault alarm)
Environmental ParametersOperating Temperature: -40°C to +70°C (non-condensing environment)Storage Temperature: -40°C to +85°CVibration Resistance: 10-500Hz frequency range, 1g acceleration (sine wave)EMC Compliance: Meets EN 55022 Class A (emission limits) and EN 55024 (immunity) standardsCertifications: CE (EMC), IEC 61508 SIL 3, UL
Product Performance
High-reliability redundant design with triple modular redundancy (TMR) architecture and 2oo3 voting logic ensures system operation even if one channel fails, with a mean time between failures (MTBF) ≥200,000 hours.
Fast response capability with 4ms output response time ensures rapid shutdown in emergencies, supporting hot-swappable functionality for maintenance without system shutdown.
High-safety certification, compliant with IEC 61508 SIL 3 standards, suitable for safety instrumented systems with safety integrity level 3.
Wide environmental adaptability with no delay in low-temperature startup at -40°C and ≤2% performance degradation at +70°C, suitable for harsh environments such as outdoors and chemical workshops.
![]()













There are no reviews yet.