GE PMC-0247RC-282000 350-93750247-282000F Switching power module
Specific Parameters
- Electrical Parameters
- Input Voltage: 100-240V AC (50/60Hz), compatible with 90-264V AC wide voltage range
- Output Voltage: 24V DC, voltage regulation accuracy ±0.5%
- Output Current: Rated 10A, maximum 12A (short-term overload, duration ≤5 minutes)
- Conversion Efficiency: ≥90% under full load (at 230V AC input)
- Ripple and Noise: ≤50mV (peak-to-peak, 20MHz bandwidth)
- Protection Functions: Overvoltage protection (28-30V DC), overcurrent protection (12-13A), short-circuit protection (self-recovery), over-temperature protection (85℃±5℃)
- Redundancy Function: Supports multi-module parallel redundancy, built-in current sharing circuit, current sharing accuracy ±5%
- Standby Power Consumption: ≤1W (230V AC input, no load)
- Environmental Parameters
- Operating Temperature: -20°C to 70°C (non-condensing, no derating during startup from -20°C to 0°C)
- Storage Temperature: -40°C to 85°C
- Relative Humidity: 5% to 95% (non-condensing, continuous operation at 90% humidity and 40°C without failure)
- EMC Immunity: Complies with EN 61000-4-2 (ESD) ±8kV contact/±15kV air, EN 61000-4-3 (RF) 10V/m, EN 61000-4-5 (surge) 2kV line-line/4kV line-earth
- Protection Class: IP20 (module itself, requires control cabinet for overall protection)
- Certification Standards: UL 60950-1 (safety of information technology equipment), CE (EMC and safety), TÜV (industrial safety certification)
- Mechanical Parameters
- Dimensions: 120mm (L) × 80mm (W) × 40mm (H, including terminals)
- Weight: Approximately 0.3kg
- Mounting Method: 35mm DIN rail snap-on mounting (compliant with EN 60715 standard)
- Housing Material: Flame-retardant reinforced plastic (UL 94 V-0 grade, oil-resistant, weak chemical corrosion-resistant)
- Terminal Type: Spring-loaded crimp terminals (compatible with 16-24 AWG wires, tool-free wiring)
- Indicators: Power Normal (PWR, green, steady on), Overload/Fault (FAULT, red, steady on/blinking), Redundancy Status (RED, yellow, on in redundancy mode)
Product Performance
Adopting high-frequency LLC resonant topology, the output voltage ripple is ≤50mV, ensuring the stability of signal acquisition and control of loads (such as sensors and I/O modules); the voltage regulation accuracy is ±0.5%, and the output voltage deviation is ≤0.12V when the input voltage fluctuates (90-264V AC) or the load changes (10%-100%). During multi-module parallel redundancy, the current sharing accuracy is ±5%, and the switching time is ≤10ms when a single module fails, with no output interruption, ensuring continuous power supply for critical equipment.
The over-temperature protection uses dual temperature sensors (chip and housing), which triggers derating at 85℃ and cuts off the output at 90℃ to avoid module burnout; the short-circuit protection is self-recovery design, which automatically restarts within 3 seconds after the fault is eliminated. The industrial-grade anti-EMC design ensures stable operation in strong electromagnetic environments (such as around frequency converters), with Mean Time Between Failures (MTBF) ≥500,000 hours (MIL-HDBK-217F, 25℃ environment).














There are no reviews yet.